| Model Number | Voltage(*1) (V) | Current (A) | Rated Power | Ripple &Noise (max) | Voltage Tolerance | Line &Load Regulation | Efficiency (Average) | Start Up Delay | |||||
| UES65LZ2-SPC | 5.0 | 0.01-3.00 | 15.00W | 200mVpk-pk | ±5% | Line:±1% Load:±5% | 82.0% | ≤3s | |||||
| 9.0 | 0.01-3.00 | 27.00W | 200mVpk-pk | ±5% | 86.8% | ≤3s | |||||||
| 12.0 | 0.01-3.00 | 36.00W | 200mVpk-pk | ±5% | 87.5% | ≤3s | |||||||
| 15.0 | 0.01-3.00 | 45.00W | 200mVpk-pk | ±5% | 88.0% | ≤3s | |||||||
| 20.0 | 0.01-3.25 | 65.00W | 200mVpk-pk | ±5% | B8.0% | ≤3s | |||||||
| Environmental | General | ||||||||||||
| Operating Temperature | 0℃ to 40℃ | Dimensions | 90.5(L)33.5(W)58.5(H)mm | ||||||||||
| Storage Temperature | -40℃ to 80℃ | Weight | 220g | ||||||||||
| Operating Humidity Storage Humidity | 10%to 90%RH,non-condensing 5%to 90%RH | MTBF | >100,000hrs MIL-HKBK-217 at 25℃ | ||||||||||
| Operating Altitude | 5,000m | ||||||||||||
| Safety Approvals | |||||||||||||
| Safety Agency /Mark | Medical(meet) | ITE(meet) | |||||||||||
| CB | IEC60601-1,IEC60601-1-11 | IEC62368-1 | |||||||||||
| UL | ANSI/AAMIES60601-1,ES60601-1-11 CAN/CSA-C22.2 N0.60601-1-11 | UL62368-1 | |||||||||||
| TUV-SUD/Mark | EN60601-1,EN60601-1-11 | ||||||||||||
| TUV-SUD/GS | EN62368-1 | ||||||||||||
| cCC | GB4943.1 | ||||||||||||
| PSE | J62368-1 | ||||||||||||
| RCM | AS/NZS62368.1 | ||||||||||||
| CE | EN62368-1 | ||||||||||||
| FCC | FCC PART15 | ||||||||||||
| BSMI | CNS14336-1 | ||||||||||||
| NOM | NOM-001-SCFI-2018 | ||||||||||||
| EMC | |||||||||||||
| Emission | Medical | ITE | |||||||||||
| Conduction | IEC/EN60601-1-2,CISPR 11 | EN55032,CISPR 32 | |||||||||||
| Radiation | IEC/EN60601-1-2,CISPR 11 | EN55032,CISPR 32 | |||||||||||
| Harmonic Currents | EN61000-3-2,Class A | EN61000-3-2,Class A | |||||||||||
| Voltage Flicker | EN61000-3-3 | EN61000-3-3 | |||||||||||
| Immunity | IEC/EN60601-1-2 | EN55035,CISPR 35 | |||||||||||
| ESD | IEC61000-4-2 ±15KV air,±8KV contact | ||||||||||||
| Radiated Immunity | IEC61000-4-3 10V/m,3V/m 80MHz-2.7GMHz | ||||||||||||
| EFT/Burst | IEC61000-4-4 ±2KVon AC port,±1KVon signal ports | ||||||||||||
| Surge | IEC61000-4-5 ±1KV line to line ,±2KVIine to GND | ||||||||||||
| Conducted Immunity | IEC61000-4-6 3Vrms,6Vrms(0.15MHz-80MHz) | ||||||||||||
| Magnetic Field | IEC61000-4-8 30 A/m | ||||||||||||
| Dips &Interruptions | IEC61000-4-11 0%,70%,0%of UT | ||||||||||||
| Others Dielectric Withstand Voltage 5,656VDC input to output Insulation Resistance 10M Ohms,500VDC input to output | |||||||||||||
We regard talents as the driving force for enterprise development and attach great importance to the selection, training, employment and retention of talents. We have also established a complete training mechanism to help each new member grow rapidly,
including basic qutraining, professional skills training, job training and management quality training. Fleming fully ensures the rapid growth of each member by creating a clear upward path and a platform space for displaying capabilities.We are always striding forward to realize the vision of "a first-class international brand enterprise with advanced
management system, excellent teamand excellent corporate culture"!